3. Switch on actuator in direction CLOSE and observe the direction of rotation on
the indicator disc.
Switch off before reaching the end position.
The direction of rotation is correct, if actuator runs in direction CLOSE and
indicator disc turns clockwise.
9.9.2 Limit switching: check
1. Set selector switch to position Local control (LOCAL).
2. Operate actuator using push buttons OPEN - STOP - CLOSE.
The limit switching is set correctly if (default indication):
- The yellow indication light/LED1 is illuminated in end position CLOSED
- The green indication light/LED5 is illuminated in end position OPEN
- The indication lights go out after travelling into opposite direction.
The limit switching is set incorrectly, if:
- The actuator comes to a standstill before reaching the end position
- One of the red indication lights/LEDs is illuminated (torque fault), or the following
fault signals are displayed:
-
Status indication S0: FAULT IND.
-
Status indication S1: TORQUE FAULT (OPEN) or TORQUE FAULT
(CLOSE)
3. If the end position setting is incorrect: Reset limit switching.
9.10 Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
54
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SG 05.1 and is the answer not in the manual?

AUMA SG 05.1 Specifications

General IconGeneral
BrandAUMA
ModelSG 05.1
CategoryController
LanguageEnglish

Related product manuals