3. Switch on actuator in direction CLOSE and observe the direction of rotation on
the indicator disc.
→
Switch off before reaching the end position.
➥
The direction of rotation is correct, if actuator runs in direction CLOSE and
indicator disc turns clockwise.
9.9.2 Limit switching: check
1. Set selector switch to position Local control (LOCAL).
2. Operate actuator using push buttons OPEN - STOP - CLOSE.
➥
The limit switching is set correctly if (default indication):
- The yellow indication light/LED1 is illuminated in end position CLOSED
- The green indication light/LED5 is illuminated in end position OPEN
- The indication lights go out after travelling into opposite direction.
➥
The limit switching is set incorrectly, if:
- The actuator comes to a standstill before reaching the end position
- One of the red indication lights/LEDs is illuminated (torque fault), or the following
fault signals are displayed:
-
Status indication S0: FAULT IND.
-
Status indication S1: TORQUE FAULT (OPEN) or TORQUE FAULT
(CLOSE)
3. If the end position setting is incorrect: Reset limit switching.
9.10 Switch compartment: open
The switch compartment must be opened to perform the following settings (options).
54
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive Modbus RTU