4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
Observe permissible cross sections.
1. Remove cable sheathing.
2. Strip wires.
3. For flexible cables: Use end sleeves according to DIN 46228.
4. Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
Connect all protective earth conductors.
Connect PE connection to external protective earth conductor of connecting
cables.
Start running the device only after having connected the protective earth con-
ductor.
5. Tighten PE conductors firmly to PE connection using ring lugs (flexible cables)
or loops (rigid cables).
Figure 12: PE connection
[1] Socket carrier
[2] Screw
[3] Washer
[4] Lock washer
[5] Protective earth with ring lugs/loops
[6]
PE connection, symbol:
Danger of corrosion: Damage due to condensation!
After mounting, commission the device immediately to ensure that heater mini-
mises condensation.
Information Some actuators are equipped with an additional motor heater.The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
18
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive Modbus RTU