EasyManuals Logo

AUMA SG 05.1 User Manual

AUMA SG 05.1
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
15.
Press again to enter the edit mode.
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT :OK C:ESC
16. Set new value:
Press .
17. Accept value or cancel?
Accept value: Press .
Cancel process without accepting the value: Press C .
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT C:ESC
AENDERN M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
18. Return to status display:
Press C several times until S0 is displayed.
9.5 Torque switching: check/set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve). .
Information The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
TORQUE (M12)
VIEW (M120)
EDIT (M121)
OPENING (M12_0)
CLOSING (M12_1)
43
SG 05.1 SG 12.1/SGR 05.1 SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU Commissioning (basic settings)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA SG 05.1 and is the answer not in the manual?

AUMA SG 05.1 Specifications

General IconGeneral
BrandAUMA
ModelSG 05.1
CategoryController
LanguageEnglish

Related product manuals