AUTOFRY Models FFG-10 and MTI-10 Operator's Manual
Semi-Annual Cleaning and Maintenance Fire
Suppression System
An inspection report / insurance certificate of installation will be forwarded to you by
mail shortly after shipment of your AUTOFRY. This document must be filed in a safe
place for future reference.
An inspection of the fire suppression system must be performed every six months
in order to comply with NFPA 96, NFPA 17A and UL 197. A certified fire equipment
maintenance company must perform this inspection.
Consult your fire suppression system manual that has been supplied with this
document for details on the inspection and re-charge instructions.
Safety System Test
The safety system must be tested a minimum of once every six months. A
qualified equipment repair technician following these instructions should
perform this inspection.
This test must be started with a full oil pot of clean cool liquid shortening.
Open the main door of the AUTOFRY and press the ON button.
• The fan will operate for approximately 10-12 seconds then shut off.
• The display will either not come on or it will read Sft.
. Individually remove each of the components listed below.
. Close the main door and press the ON button.
• The fan will operate for approximately 10-12 seconds then shut off.
• The display will either not come on or it will read Sft.
1. The filter cover plate.
2. The grease baffle.
3. The second filter.
4. The charcoal filter.
5. The removable fire damper / stack cover.