EasyManuals Logo

Automated Logic RC642D User Manual

Automated Logic RC642D
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
69
If chilled water is used, the Room Controller measures the zone temperature and
modulates the chilled water valve to maintain the cooling setpoint.
The cooling analog output opens to 50% when the freezestat is on.
Cooling is enabled when:
The unit is running, and
The fan status is on, and
The unit is not heating.
Heating
If staged heating is used, the Room Controller measures the zone temperature and turns
on the heating as needed to maintain the heating setpoint. To prevent short cycling, the
heating stage has a 1-minute minimum runtime.
If hot water heating is used, the Room Controller measures the zone temperature and
modulates the heating analog output to maintain the heating setpoint.
The heating analog output opens to 100% when the freezestat is on.
Heating is enabled when:
The unit is running, and
The fan status is on, and
The unit is not cooling.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automated Logic RC642D and is the answer not in the manual?

Automated Logic RC642D Specifications

General IconGeneral
BrandAutomated Logic
ModelRC642D
CategoryController
LanguageEnglish

Related product manuals