6 Parameter Settings and Functions 
© Copyright Reserved Autonics Co., Ltd.    83 
6.4.7  Loop Break Alarm [PAR4 → AL-1/AL-2 → LBA] 
  Diagnoses the control loop by monitoring the control subject's temperature changes 
and sends out alarms if necessary. 
  Heating control: When control output MV is 100% or high limit (H-MV) and PV is not 
increased over than LBA detection band (
LBA.B)during LBA monitoring time (LBA.T), 
or when control output MV is 0% or low limit (
L-MV) and PV is not decreased below 
than LBA detection band (
LBA.B) during LBA monitoring time (LBA.T), alarm output 
turns ON.   
  Cooling control: When control output MV is 0% or low limit (L-MV) and PV is not 
increased over than LBA detection band (
LBA.B) during LBA monitoring time (LBA.T), 
or when control output MV is 100% or high limit (
H-MV) and PV is not decreased 
below than LBA detection band (
LBA.B) during LBA monitoring time (LBA.T), alarm 
output turns ON. 
Common Causes of LBA Output On 
  Sensor Error (disconnection, short) 
  External Controller Error (magnet, auxiliary relay, etc.) 
  External Load Error (heater, cooler, etc.)   
  Misconnections and disconnections of external network. 
 
  Set alarm output mode(
) as loop break alarm (
) and you 
can use loop break alarm.     
  LBA operates only when control output MV is low limit (
), 0%, 
high limit (
), or 100%.     
  In case of AT (auto-tuning)/manual control/stop control, loop break 
alarm (
) does not operates   
  When alarm reset is input, it initializes LBA monitoring start time.     
6.4.7.1  LBA Monitoring Time [PAR4 → LBA.T] 
You can set the LBA monitoring time to check changes in the control subject's 
temperature.   
Automatically setting with auto-tunning. 
Setting 
Group 
Parameter  Setting Range 
Factory 
Default 
Unit 
to 
Sec