6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 99
Ignores MV from ON/OFF control or PID control and sends out a control
value based on the defined MV.
6.7.2.2 Stop Alarm Output [PAR5 ST.AL]
Enable or disable alarm output upon a stop.
Setting Description
OFF
Alarm output ceases along with a stop under all conditions.
(However, reverting to Run mode after a stop in alarm latch or alarm
latch and standby sequence restores the alarm output to the
previous state.)
CONT
Alarm output continues regardless of control operation.
Setting
Group
Parameter Setting Range
Factory
Default
Unit
PAR1
R-S
CONT
/
OFF
CONT
-
6.7.3 Multi SV
Multi SV function allows users to set multiple SVs and save each setting in SV0 to
SV3. Users can change SV-N or select desired SV using external DI (Digital Input, DI-
1, DI-2) terminals.
This feature supports up to four SVs which can be independently configurable.
6.7.3.1 Number of Multi SVs [PAR5 MT.SV]
This parameter sets the number of Multi SVs. Select the number of Multi SVs required by
the control subject.
Number of SVs SV Assignment
1 EA
SV-0
2 EA
SV-0, SV-1
4 EA
SV-0, SV-1, SV-2, SV-3,
Setting
Group
Parameter Setting Range
Factory
Default
Unit
PAR5
MT.SV
1
/
2
/
4
1
EA
If the Digital Input (, ) feature has been set for multi SV (MT.SV),
the number of Multi SV(MT.SV) is not modified through pressing key or
communication.

Table of Contents

Other manuals for Autonics TK4M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TK4M and is the answer not in the manual?

Autonics TK4M Specifications

General IconGeneral
BrandAutonics
ModelTK4M
CategoryTemperature Controller
LanguageEnglish

Related product manuals