37
6.4 Table IIC
Level II Program Values - 962 Twin Tank Alternating Softener (P17=2)
Parameter
Description of
Program Values
Range of Values
Min.
Increment
Factory
Value
Units of Measure Notes
P1 Day of Week and
Time of day
(1-7) 1:00 - 12:59
AM or PM
Metric
(1-7) 0:00 - 23:59
(1 day)
1 minute
None Hour
Minute
Range depends on value selected for
P13. For day of week SUN=1, MON=2,
TUE=3, WED=4, THU=5, FRI=6, SAT=7.
THIS IS THE LEFT MOST DIGIT ON
THE DISPLAY.
P2 Time of day to start
regeneration
1:00 - 12:59 AM or PM
00:00 - 23:59
1 None Hour
Minute
Range depends on value selected for
P13. Use only if P15 =1
P3 Hardness of water 3-250
30-2500
1
10
0
0
Grains per gallon
ppm
Unit of measure depends on value
selected for P12
P4 Salt amount 5 – 1250
2 - 500
5
2
10
4
Pounds
Kilograms
Unit of measure and factory value
depend on value selected for P12
P5 Capacity of unit 1-2600
0.1-260.0
1
0.1
0 Kilograins
Kilograms
Total capacity for each tank. Unit of
measure depends on value selected for
P12
P6 Refill controller 2 - 99 1 0 Selected from chart in
Performance Data Sections, page 57
P7 Brine draw rate 2 - 99 1 0 Selected from chart in
Performance Data Sections, page 58
P9 Backwash time 4 - 30 1 14 Minutes
P10 Rinse time 7 - 125 1 40 Minutes
P11 Purge time 2 - 19 1 4 Minutes
P12 Units of measure 0 - 1 1 0 0 = US, 1 = Metric
P13 Clock mode 0 - 1 1 0 0 = 12 hour clock, 1 = 24 hour clock
P14 Calendar override 0 - 30 1 0 Days 0 = no calendar override
P15 Regeneration
delay
0 - 1 1 0 0 = Immediate regeneration
1 = Regeneration delayed until time pro-
grammed in P2 is reached
P16 Capacity that must
be left on 2nd tank
to permit delayed
regeneration of 1st
tank
0 - 70 1 30 Percent of Total
capacity
Used only if P15 is set to 1
P17 Operation type 0 - 2 1 2 2 = Twin Alternating
P18 Salt/Capacity
Change Lock Out
0 - 1 1 0 0 = none 1 = Salt /Capacity Change
Locked Out
P19 Flow Sensor select 0 0 = Magnum IT NHWB, 1 = 1.0" Autotrol
Turbine, 2 = 2.0” Autotrol Turbine, 3 =
User defined
K-factor, 4 = User defined pulse
equivalent, 5 = Magnum IT HWB
P20 K-factor or Pulse
equivalent
0.01 -255.00 .01 0.01 Number used for Meter K-factor or Pulse
equivalent
P21 Remote
Regeneration
Switch Delay
1 - 254 1 60 Seconds Time remote switch must be active to
start a regeneration.
P22 Factory Use Only
DO NOT
CHANGE
99
Do not change

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autotrol Magnum Cv 942F and is the answer not in the manual?

Autotrol Magnum Cv 942F Specifications

General IconGeneral
BrandAutotrol
ModelMagnum Cv 942F
CategoryControl Unit
LanguageEnglish

Related product manuals