In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 36
Step Actions to be taken Display Indication Audible Indication
point has been set to
Override Delay and
Dependency YES).
8
Carry out the necessary
actions.
9
To silence all alarms,
press the red Silence
button.
All Fire Alarm Devices
(FAD) are deactivated.
Comments: The red Alarm indicator goes steady.
To manually resound the alarm zones at this stage, press and hold down the
Silence button at least 5 seconds.
Configurable: A timer begins to count down. The alarm zones can be
automatically resounded to their alarm states on timeout of the silence
resound timer.
When the fire is extinguished and all necessary repair work is implemented
(smoke is exhausted, new glass replaced in the manual call-points, etc.), the
system should be returned to normal operation mode.
10
Press the green Reset
button.
All audible indicators on
all panels in the system
are turned off.
If no points are signalling an alarm, the system is reset and the display will return to its idle state.
Comments: The red Alarm indicator goes off.
The red Remote Call indicator goes off (if a FARE output is configured and
applied).