7-8
7-5  FM Intrinsically safe (ic) and Nonincendive 
Intrinsically safe(ic)
Class I, Zone 2, AEx ic IIC T4
Entity Parameters:
Positioner Circuit: Ui=30V, Ii=100mA, Pi=1W, Ci=24nF, Li=0.22mH
Transmitter Circuit  (AVP701): Ui=30V, Ii=100mA, Pi=1W, Ci=20nF, Li=0.22mH
Nonincendive
Class I, Division 2, Group A, B, C and D, T4
Nonincendive Field Wiring Parameters:
Positioner Circuit: Vmax=30V, Imax=100mA, Ci=24nF, Li=0.22mH
Transmitter Circuit  (AVP701): Vmax=30V, Imax=100mA, Ci=20nF, Li=0.22mH
Suitable
Class II and Class III, Division 2, Group E, F and G, T4
Indoor/Outdoor Enclosure
NEMA Type 4X, IP66
Ambient Temperature:-24 to 75
Instruction for safe use
-   Models AVP701/ AVP702 shall be installed in accordance with control drawings 
80396167 and 80396168.
-   Installations in the US shall comply with the relevant requirements of the 
National Electrical CodeR (ANSI/NFPA-70 (NECR).
-   Tampering and replacement with non-factory components may adversely affect 
the safe use of the system.
-   For guidance on installation in the US, see ANSI/ISA-RP12.06.01, Installation of 
Intrinsically Safe Systems for Hazardous (Classified) Locations.
-   Electrical equipment connected to the Associated Apparatus shall not use or 
generate more than 250 Volts rms.
-   The products discussed in this report were certified by FM Approvals under a 
Type3 Certification System as identified in ISO Guide 67.