3-12
3-2-3 Supply Bypass
Supply bypass allows the valve to be fully closed and opened and enables operation with
the regulator.
(For double-acting actuators, the valve can only be fully opened or closed.)
Cautions
When the supply bypass operates, it is dangerous because the valve moves. Be
prepared in advance to prevent injury and effects on the process when the valve moves.
(1) Procedure for supply bypass
Step Work LUI display
1
Loosen two (2.5-mm) hexagonal socket bolts and
remove the front cover.
2
Hold down to enter setting mode. If a
password is required, enter the password.
For details on password entry refer to 3-2-5,
“Password.”
3
Press the
button to display the screen shown
on the right.
4
Press the
button to go to the screen shown
on the right. To set the output air pressure to 0,
hold down the
button.
(If the output air pressure is already 0 or it is set
to the supply air pressure at the supply bypass,
go to the screen of step 7 where the supply
bypass can be operated.)
5
To change the output air pressure to the supply
air pressure, press the
button to display the
screen on the right and hold down the
button.
6
If supply bypass conditions (e.g. the input signal
is less than 5 mA) are not satisfied, the screen on
the right is displayed.
7
If supply bypass conditions are satisfied, the
screen shows that each bypass operates.
8
To clear supply bypass operations, press the
button to display the screen shown on the right.
9
Holding down the button clears the supply
bypass.