EasyManua.ls Logo

Azbil 700 series - Display on the Local User Interface (LUI)

Azbil 700 series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-7
1-4-3 Display on the Local User Interface (LUI)
3
6
7
1
10
5
8
9
2
4
Figure1-8 Segments on the LCD
Table 1-3 Description of Each Part
No. Displayed element Main display
(1) 7 segments (5 digits) Displays the main numerical values such as the specified opening.
(2) Minus sign Displays the sign for the 7-segment number.
(3)
Decimal point
(five places)
Displays the decimal point for the 7-segment number.
(4)
16 segments
(7 digits)
Displays the unit, status, or other data.
(5) Dot (6 places) Displays the 16-segment auxiliary display, separator, or other data.
(6) Percentage Displays %.
(7) Bar graph (22 bars) Displays the bar graph in percentage at a set point, etc.
(8) Key mark
On: LUI operation is unavailable.
Off: LUI operation is available.
Blinking: LUI is in operation.
(9) Flag mark
When the self-diagnostic alarm is activated, the key mark is displayed.
For detailed information of the alarms,please refer to the status monitor of
page 3-4.
(10) Display refresh mark
Display during operation
White and black circles alternately blink.
For a display example, refer to "LUI Display List" in Appendix A.
Handling Precautions:
The LUI buttons may not respond well near an electromagnetic inductor (such as
a large transformer or high-frequency furnace).
Remove sand, dust, and other foreign objects from the rubber parts of the
operation buttons before operating the LUI. Operating the LUI with foreign
objects on it may damage the rubber parts.
Do not pull the rubber parts of the operation buttons. This may deteriorate the
sealability, possibly causing malfunction.