6-2
6-1  A/M Switch
The maintenance work can be performed by switching between Auto and Manual. The 
device has a built-in Auto/Manual (A/M) switch.
The A/M switch switches the control method of output air from the positioner between 
auto operation and manual operation.
1)  Auto operation
•  The device outputs the output air pressure to control the opening according to the 
input signal.
2)  Manual operation
•  The positioner directly outputs the supply air pressure.
•  Manual operations with the regulator are possible. (The double-acting actuator does 
not support manual operation.)
Warning
It is dangerous because the valve moves when the A/M switch is operated. Be 
prepared in advance to prevent injury and effects on the process when the valve 
moves.