3-13
The ‘FAIL signs in the supply bypass operation are as follows.
FAIL01: The input signal is low level.
FAIL02: A function except for the supply bypass is in operation.
FAIL90: The auto setup is forcibly shut down.
3-2-4 Control Parameters
Control parameters are determined by Actuator Size (Param 1 to 6, A, B, C) and
Friction Level (Light(L), Medium(M), Heavy(H)).
Table3-2 Actuatorsize
Actuator Size Stroke Speed[s] Actuator Model
Actuator
Diaphragm
capacity[cm
3
]
PARAM C to 0.25 - 200
PARAM B to 0.35 - 300
PARAM A to 0.45 - 400
PARAM 1 to 0.85 PSA1, PSK1 600
PARAM 2 to 2.0 PSA2, HA2 1400
PARAM 3 to 6.5 PSA3, HA3 2700
PARAM 4 to 8.15 PSA4, HA4 6600
PARAM 5 to 12 PSA6 8100
PARAM 6 to 99 VA5 25300
Custom - - *
* Consult an Azbil Corp. service representative.
Table3-3 FrictionLevel
Friction Level Gland packing material example
HEAVY Graphite packing
MEDIUM Yarn packing
LIGHT Type V PTFE packing
* This is not decided with the materials in a parameter to be decided by frictional force of the grand packing.
Cautions
It is dangerous because the valve moves when control parameters are changed. Be
prepared in advance to prevent injury and effects on the process when the valve moves.