4-13
4-2-13 Adjustment of EPM Drive Signal (Pneumatic Modules)
This function is used to adjust the EPM drive signal if the signal has shifted or if
Positioner Action has changed.
Select [Device] → [Maintenance] → [Pneumatic Modules] → [EPM Adjustment].
Handling Precautions:
Ask our service representative for the operation not to damage a device by
erroneous operation..
4-2-14 Restore factory settings
Restore the data that was set when the device was shipped from the factory.
Select [Device]→[Maintenance]→[Restore factory settings].
(It may be necessary to restart the communication tool after restoring the factory data.)
Handling Precautions:
This operation does not change the HART communication settings such as
Device Tag and Long Tag, diagnostics-related settings, and history information.
4-2-15 Operator Action Records
Save the history of setting modification operations.
The operation item, operation method, and time of the last 10 modifications are saved.
Simulation operations are not saved.
Select [Device]→[Maintenance]→[Operator Action Records].
4-2-16 Real Time Clock
Checks and sets the current time.
Select [Device] → [Maintenance] → [Real Time Clock].
Handling Precautions:
The current time set with this operation is reset when the power is cut.
(2012/04/01 00:000)
4-2-17 Password
Sets whether to use the password function and sets the password.
Select [Device] → [Maintenance] → [Password].