7-13
7-6 FMC Explosionproof / Dust Ignition Protection
Explosionproof
Class I, Division 1, Group C and D T6;
Flameproof
Class I, Zone 1, Ex d IIB T6 Gb
Dust ignition
Class II and III, Division 1, Group E, F, and G
T6;
Ambient temperature : -30 to +75 °C
Indoor/Outdoor Enclosure IP66
WARNING
• Install the apparatus only in hazardous (classified) locations for which the
apparatus has been approved.
• For division applications:
Factory sealed, conduit seal not required
Not including gasoline atmospheres
• For zone applications
Seal all conduits within 450mm (18 INCHES)
• Do not open the apparatus enclosure when an explosive atmosphere is present.
CAUTION
Use supply wires suitable for 5°C above surrounging ambient.
Sealing
compound
Y
Plug
Conduit
18 inches (450 mm)
Maximum distance