3-14
(1) Procedure for specifying control parameters
Step Work LUI display
1
Loosen two (2.5-mm) hexagonal socket bolts and
remove the front cover.
2
Hold down the
button to start the setup mode.
Enter the password if prompted to do so. For how
to enter the password, refer to "3-2-5 Password".
3
Press the button to display the screen shown
on the right (tune).
4
Press the
button to display the screen on
the right and select Param 1 to 6, A, B, or C for
Actuator Size by operating the
button, and
press the
button.
5
Select L (Light), M (Medium), or H (Heavy) for
Friction Level and set it by holding down the
button.
To return the setting to its original value, reset
the value with
before holding down the
button.
6
Check the specification result when it is
displayed.