3-7
(1) Procedure for performing auto setup
Step Work LUI display
1
Loosen two (2.5-mm) hexagonal socket bolts and remove 
the front cover. (A sample initial setup status of the LUI 
screen is shown.)
2
Press and hold the   button to enter Settings mode. 
Enter the password if prompted to do so. For how to set the 
password, refer to "3-2-5 Password". To change Actuator 
Type or Valve Closed Position, refer to step (3).
3
Wait until the input signal becomes at least 5 mA and press 
the
   
button once. Check that the screen on the right 
is displayed and press and hold the 
 
button again to 
perform auto setup.
4
The valve, which is initially fully closed, is fully opened and 
fully closed again. Then, it is opened to between 20% and 
25% and between 80% and 85%. After the valve operation 
ends, the LUI screen changes and the opening appropriate 
to the input signal is set.
5
When you press the   button, the initial screen of the 
auto setup is displayed again.
The ‘FAIL’ signs in the auto setup operation are as follows.
  FAIL00: The auto seuup is failed. (The valve does not move, etc.)
  FAIL01: The input signal is low level.
  FAIL02: A function except for the auto setup is in operation.
  FAIL90: The auto setup is forcibly shut down. (Auto setup was stopped from the LUI.)
  For countermeasures for these problems, refer to 5-1-5, “Auto Setup Failure.”
(2) Procedure for aborting auto setup
Step Work LUI display
1 To abort auto setup during execution, press the 
 button.
2
Holding down the   button aborts the execution.
If auto setup is aborted, data is not saved.
3
When you press the
 
 
button, the screen on the right is displayed 
again.