EasyManua.ls Logo

Azbil 700 series - Page 98

Azbil 700 series
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-12
No.
Name Part no. Qty.
Recommended
replacement
period
(year)*1
Recommended
tightening torque
N·m
27 O-ring (AS568-012) (for A/M screw) 80020935-325 1 5 -
28 Feedback lever assembly
80377049-001 (without
option M6)
80377049-002 (with
option M6)
1 - -
29 Feedback lever
80377148-001 (with
option M6)
80377148-002 (without
option M6)
1 - -
30 Arm spring
80377149-001 (with
option M6)
80377149-002 (without
option M6)
1 - -
31
Hexagon socket bolt with captive spring
washer (for feedback lever, M5×8)
80377127-001
2
(4)*2
- 2.9 ± 0.3
32 Extension lever
80377142-001 (40mm
extension, without option
M6)
80377142-101 (40mm
extension, with option
M6)
80377142-002 (80mm
extension, without option
M6)
80377142-102 (80mm
extension, with option
M6)
1 - 2.9 ± 0.3
33
Blind plug/pressure-resistant explosion-proof
plug (G1/2)
80377115-001 1 5 -
34 Blind plug/plug (for general use, NPT1/2) 80277971-001 1 - -
35 Blind plug/plug (for IECEx/ATEX, NPT1/2) 80372545-001 1 - -
36 Blind plug/plug (for general use/ATEX, M20) 80377205-001 1 5 -
37 Blind plug/plug (for IECEx, M20) 80372699-001 1 5 -
38 Flameproof cable gland 80388728-002
1
(2)*3
10 -
39 Flameproof elbow (G1/2) 80357206-108
1
(2)*3
10 -
100 LCD cover 80384067-001 1 10 -
101 Pressure gauge elbow 80384049-001
2
(3)*4
- -
*1 The recommended replacement period assumes standard conditions (JIS C 1804, C 1805). The replacement period may be
shorter depending on environmental conditions (such as temperature, humidity, vibration, and air quality) and usage conditions
(such as operation frequency and ON/OFF operations).
*2 If the extension lever is required.
*3 When using two conduit connection ports.
*4 When Pilot Relay Type is set to Double Acting.

Table of Contents

Related product manuals