6-12
No.
Name Part no. Qty.
Recommended
replacement
period
(year)*1
Recommended
tightening torque
N·m
27 O-ring (AS568-012) (for A/M screw) 80020935-325 1 5 -
28 Feedback lever assembly
80377049-001 (without
option M6)
80377049-002 (with
option M6)
1 - -
29 Feedback lever
80377148-001 (with
option M6)
80377148-002 (without
option M6)
1 - -
30 Arm spring
80377149-001 (with
option M6)
80377149-002 (without
option M6)
1 - -
31
Hexagon socket bolt with captive spring
washer (for feedback lever, M5×8)
80377127-001
2
(4)*2
- 2.9 ± 0.3
32 Extension lever
80377142-001 (40mm
extension, without option
M6)
80377142-101 (40mm
extension, with option
M6)
80377142-002 (80mm
extension, without option
M6)
80377142-102 (80mm
extension, with option
M6)
1 - 2.9 ± 0.3
33
Blind plug/pressure-resistant explosion-proof
plug (G1/2)
80377115-001 1 5 -
34 Blind plug/plug (for general use, NPT1/2) 80277971-001 1 - -
35 Blind plug/plug (for IECEx/ATEX, NPT1/2) 80372545-001 1 - -
36 Blind plug/plug (for general use/ATEX, M20) 80377205-001 1 5 -
37 Blind plug/plug (for IECEx, M20) 80372699-001 1 5 -
38 Flameproof cable gland 80388728-002
1
(2)*3
10 -
39 Flameproof elbow (G1/2) 80357206-108
1
(2)*3
10 -
100 LCD cover 80384067-001 1 10 -
101 Pressure gauge elbow 80384049-001
2
(3)*4
- -
*1 The recommended replacement period assumes standard conditions (JIS C 1804, C 1805). The replacement period may be
shorter depending on environmental conditions (such as temperature, humidity, vibration, and air quality) and usage conditions
(such as operation frequency and ON/OFF operations).
*2 If the extension lever is required.
*3 When using two conduit connection ports.
*4 When Pilot Relay Type is set to Double Acting.