5-3
Chapter 5. SETTINGS BEFORE STARTING OPERATION
z
PV input range table (Thermocouple)
z
PV input range table (RTD)
C0
1
set value
Sensor
type
Range
(Celsius)
Range
(Fahrenheit)
C04
display
C04
range
C04 initial value
when C0
1 settings
C0
1
set value
Sensor
type
Range (Celsius) Range
(Fahrenheit)
C04
display
C04
range
C04 initial value
when C0
1 settings
1 K -200 to +1200˚C
-300 to + 2200˚F
---- (Not setting) (No decimal point) 41 Pt100
-200.0 to +500.0˚C
-300 to + 900˚F ---- (Not setting) (No decimal point)
2 K 0 to 1200˚C 0 to 2200˚F ---- (Not setting) (No decimal point) 42 JPt100
-200.0 to +500.0˚C
-300 to + 900˚F ---- (Not setting) (No decimal point)
3 K 0.0 to 800.0˚C 0 to 1500˚F
0 to 1 0 43 Pt100
-200.0 to +200.0˚C
-300 to + 400˚F ---- (Not setting) (No decimal point)
4 K 0.0 to 600.0˚C 0 to 1100˚F
0 to 1 0 44 JPt100
-200.0 to +200.0˚C
-300 to + 400˚F ---- (Not setting) (No decimal point)
5 K 0.0 to 400.0˚C 0 to 700˚F
0 to 1 0 45 Pt100
-100.0 to +300.0˚C
-150 to + 500˚F ---- (Not setting) (No decimal point)
6 K
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1 0 46 JPt100
-100.0 to +300.0˚C
-150 to + 500˚F ---- (Not setting) (No decimal point)
9 J 0.0 to 800.0˚C 0 to 1500˚F
0 to 1 0 51 Pt100
-50.0 to +200.0˚C
-50 to + 400˚F
0 to 1 1
10 J 0.0 to 600.0˚C 0 to 1100˚F
0 to 1 0 52 JPt100
-50.0 to +200.0˚C
-50 to + 400˚F
0 to 1 1
11 J
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1 0 53 Pt100
-50.0 to +100.0˚C
-50 to + 200˚F
0 to 1 1
13 E 0.0 to 600.0˚C 0 to 1100˚F
0 to 1 0 54 JPt100
-50.0 to +100.0˚C
-50 to + 200˚F
0 to 1 1
14 T
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1 0 63 Pt100 0.0 to 200.0˚C 0 to + 400˚F
0 to 1 1
15 R 0 to 1600˚C 0 to 3000˚F ---- (Not setting) (No decimal point) 64 JPt100 0.0 to 200.0˚C 0 to + 400˚F
0 to 1 1
16 S 0 to 1600˚C 0 to 3000˚F ---- (Not setting) (No decimal point) 67 Pt100 0.0 to 500.0˚C 0 to + 900˚F ---- (Not setting) (No decimal point)
17 B 0 to 1800˚C 0 to 3300˚F ---- (Not setting) (No decimal point) 68 JPt100 0.0 to 500.0˚C 0 to + 900˚F ---- (Not setting) (No decimal point)
18 N 0 to 1300˚C 0 to 2300˚F ---- (Not setting) (No decimal point)
19 PL II 0 to 1300˚C 0 to 2300˚F ---- (Not setting) (No decimal point)
20 WRe5-26 0 to 1400˚C 0 to 2400˚F ---- (Not setting) (No decimal point)
21 WRe5-26 0 to 2300˚C 0 to 4200˚F ---- (Not setting) (No decimal point)
23 PR40-20 0 to 1900˚C 0 to 3400˚F ---- (Not setting) (No decimal point)
24 DIN U
-200.0 to +400.0˚C
-300 to + 700˚F
0 to 1 0
25 DIN L
-100.0 to +800.0˚C
-150 to + 1500˚F
0 to 1 0
*1. Accuracy of sensor type B (No.17): ±5 %FS below 260 ˚C, ±1%FS from 260 to 800 ˚C, not specified below 20 ˚C
However, if ROM version 1 in the instrument information bank (
i
d02
) is 2.04 or earlier, the low limit for display is -180 ˚C.
Accuracy of sensor type PR40-20 (No.23): not specified below 300 ˚C, ±5 %FS from 300 to 800 ˚C, ±2 %FS from 800 to
1900 ˚C
However, if ROM version 1 in the instrument information bank (
i
d02
) is 2.26 or earlier, No.23 cannot be selected.
*2. PL II thermocouple is a range, which has been added to the units manufactured from July, 2003.
*3. The PV range display for thermocouple with a decimal point is available for ROM version 2.26 and later.
z
PV input range table (DC voltage/DC current)
C0 1
set value
Sensor type
Range (C05, C06) C04
display
C04
range
C04 initial value
when C01 settings
84 0 to 1 V
• Scaling range is -1999 to +9999.
• When C01 is changed, the
range (C05, C06) defaults to 0
to 1000.
0 to 3 No change
86 1 to 5 V
0 to 3 No change
87 0 to 5 V
0 to 3 No change
88 0 to 10 V
0 to 3 No change
89 0 to 20 mA
0 to 3 No change
90 4 to 20 mA
0 to 3 No change
Handling Precautions
• When the C01 PV input range number is set, the decimal point position and
range are initially set automatically as shown in the tables. For details on the
decimal point, refer to;
Decimal point position setup (p.5-5)
• Make sure to set the correct number in setup display C01, according to the
type and range of the sensor used. If the setting is wrong, problems such as
large temperature errors in the output may occur.
• For details about the accuracy of each PV range type, refer to;
Chapter 11. SPECIFICATIONS (p.11-1).