5-4
Chapter 5. SETTINGS BEFORE STARTING OPERATION
Temperature unit setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 s or longer.
>>
The display is then changed to the setup setting
display.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [para] key.
>>
The setup setting [C02: Temperature unit] is
displayed.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(4) Press the [<], [
], or [
] key to set the value you have
selected from the following in [C02].
0: Centigrade (°C)
1: Fahrenheit (°F)
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>>
The display is returned to the operation display.
Handling Precautions
When the input type of the model is "T: Thermocouple" or "R: RTD", [C02:
Temperature unit] can be displayed. However, when the input type is "L: DC
current or DC voltage", [C02] cannot be displayed.