5-22
Chapter 5. SETTINGS BEFORE STARTING OPERATION
Event main setting setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) Press the [para] key several times.
>>
Display the parameter setting [E1: Internal Event 1
main setting].
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [<], [
], or [
] key to change the set value in
[E1].
Setting range: -1999 to +9999
The decimal point position is changed corresponding to the event operation type.
For a part of the event operation types, the setting range becomes 0 to + 9999.
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>>
The display is returned to the operation display.
Handling Precautions
• The displays of the internal event 2 to 5 main settings are [E2], [E3], [E4],
and [E5].
• When the internal event operation type is set at [0: No event] or the
operation type does not need any main setting, the internal event main
setting is not displayed.