Receiving & Installation 3-5
MN1276
Table 3 -1 Wire Size and Protection Devices (for units with Power Supply)
Catalog Number Incoming Power
In
ut
Nominal In
ut
Continuous
Input
Fuse
re
auge
Voltage
Output
Amps
(RMS)
Breaker
(A)
Time
Delay (A)
AWG
(USA)
mm
2
(Europe)
FP1A02SR-XXXX
115V (1Ô)
2.0A 7.5 8 14 2.5
FP2A02SR-XXXX
230V (3Ô)
2.5A 7 4.5 14 2.5
FP1A02TR-XXXX
115V (1Ô)
2.0A 7.5 8 14 2.5
FP2A02TR-XXXX
230V (1Ô)
2.5A 5 4.5 14 2.5
FP4A02TB-XXXX
400/460V (3Ô)
2.5A 7 4 14 2.5
FP1A05SR-XXXX
115V (1Ô)
5A 7.5 8 14 2.5
FP1A05SR-XXXX
230V (3Ô)
5A 7 8 14 2.5
FP1A05TR-XXXX
115V (1Ô)
5A 7.5 8 14 2.5
FP2A05TR-XXXX
230V (1Ô)
5A 7.5 7 14 2.5
FP4A05TB-XXXX
400/460V (3Ô)
5A 7 7.5 14 2.5
FP1A07TR-XXXX
115V (1Ô)
7.5A 10 10 14 2.5
FP2A07TR-XXXX
230V (1Ô)
7.5A 10 10 14 2.5
FP4A07TR-XXXX
400/460V (3Ô)
7.5A 15 12 14 2.5
FP1A10SR-XXXX
115V (1Ô)
10A 12.5 15 14 2.5
FP2A10SR-XXXX
230V (3Ô)
10A 15 15 14 2.5
FP1A15SR-XXXX
115V (1Ô)
15A 20 20 12 2.5
FP2A15SR-XXXX
230V (3Ô)
15A 20 25 12 2.5
FP4A15TR-XXXX
400/460V (3Ô)
15A 20 20 12 2.5
FP4A20TR-XXXX
400/460V (3Ô)
20A 30 35 10 5.26
FP4A27TR-XXXX
400/460V (3Ô)
27.5A 40 45 10 5.26
Table 3-2 Wire Size (for units without Power Supply)
a
a
og
um
er
Continuous
re
auge
Bus
Voltage
Output
Amps
AWG
(USA)
mm
2
(Europe)
FP1A02PO-xxxx 160VDC 2.0A 14 2.5
FP2A02PO-xxxx 300VDC 2.5A 14 2.5
FP1A05PO-xxxx 160VDC 5.0A 14 2.5
FP2A05PO-xxxx 300VDC 5.0A 14 2.5
FP1A10PO-xxxx 160VDC 10.0A 12 2.5
FP2A10PO-xxxx 300VDC 10.0A 12 2.5
FP1A15PO-xxxx 160VDC 15.0A 10 2.5
FP2A15PO-xxxx 300VDC 15.0A 10 2.5
Note: All wire sizes are based on 75#C copper wire. Higher temperature smaller gauge wire may
be used per NEC and local codes. Recommended fuses/breakers are based on 25#C
ambient, maximum continuous control output current and no harmonic current.
X1 Power Connections
Power connections are shown in Figures 3-5 through 3-8.