EasyManuals Logo

Baldor FPX A05T User Manual

Baldor FPX A05T
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
Receiving & Installation 3-21
MN1276
X8 Resolver Feedback The r esolver connections are the standard feedback on Flex+ drives and
connections are made at the X8 connector as shown in Figure 3-27. The resolver
cable must be shielded twisted pair #22 AWG (0.34mm
2
) wire minimum. The
cable must also have an overall shield. Maximum wire-to-wire or wire-to-shield
capacitance is 50pf per foot.
Resolver wiring must be separated from power wiring. Separate parallel runs of
resolver and power cables by at least 3'. Cross power wires at right angles only.
Insulate or tape ungrounded end of shields to prevent contact with other
conductors or ground.
Note: Motor and resolver are phase sensitive. Connect only as instructed.
Figure 3-27 Resolver Cable Connections for UL Installations
P
3SIN+
8SIN-
2COS+
7COS-
1REF+
6 REF- (Common)
Shell (Chassis)
P
P
P
=TwistedPair
R2
R1
S2
S4
S1S3
X8
Shields
Figure 3-28 Resolver Cable Connections for CE Installations
P
3SIN+
8SIN-
2COS+
7COS-
1REF+
6 REF- (Common)
P
P
P
=TwistedPair
R2
R1
S2
S4
S1S3
X8
5AGND
Connect overall shield
to connector backshells
Connect internal
shields to AGND

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baldor FPX A05T and is the answer not in the manual?

Baldor FPX A05T Specifications

General IconGeneral
BrandBaldor
ModelFPX A05T
CategoryServo Drives
LanguageEnglish

Related product manuals