EasyManua.ls Logo

Basler BE1-11m - Page 362

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62-2 9424200996
Instantaneous Undercurrent (37) Test BE1-11m
OUT2 closes for 37 Pickup.
Fault recording is enabled.
Figure 62-1. BESTlogicPlus Settings
Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Undercurrent (37) screen
and send the low range test settings (minimum pickup setting) to the BE1-11m for your sensing
input type in Table 62-2.
Table 62-2. Pickup Test Settings
Sensing Input Type Range Pickup Setting Time Delay
5 A
Low
0.5 A
0 ms
Middle
5.0 A
0 ms
High
20.0 A
0 ms
1 A
Low
0.1 A
0 ms
Middle
1.0 A
0 ms
High
4.0 A
0 ms
Step 4: Prepare to monitor the 37 function operation. Operation can be verified by monitoring OUT2
(see Figure 62-1).
Step 5: Connect a current source and apply 0.6 Aac to terminals D1 and D2 (A-phase). Note that IA, IB,
or IC can be used for this test. Test is conducted on IA.
Step 6: Slowly decrease the A-phase current until OUT2 closes and record pickup. Verify the 37-1
target on the front-panel display. Slowly increase the applied current until OUT2 opens and
record reset.
Step 7: Repeat step 6 for the middle and high range pickup settings for your sensing input type. Record
the results.
Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.
Step 9: (Optional.) Repeat steps 1 through 8 with CT Circuit 2 as the source for protection systems
equipped with two sets of CTs. In step 5, replace D1 with F1, D2 with F2, etc.
Timing Verification
Step 1: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Undercurrent (37) screen
and send the first row of test settings in Table 62-3 to the BE1-11m for settings group 0.
Table 62-3. Timing Test Settings
Pickup Setting
Time Delay
0.5 A
2000 ms
0.5 A
5000 ms
0.5 A
10000 ms

Table of Contents

Related product manuals