EasyManua.ls Logo

Basler BE1-11m - Page 386

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65-6 9424200996
Inverse Overcurrent (51) Test BE1-11m
Pickup Verification (I2 Mode)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 65-9 to the BE1-11m. Reset all
targets.
Table 65-9. Operational Settings (I2 Mode)
Setting
Value
BESTCOMSPlus Screen
Description
Phase CT
Ratio
1
System Parameters, Sensing
Transformers
Sets phase CT ratio to 1
Element
Mode
I2
Protection, Current, Instantaneous
Overcurrent (51-1)
Enables 51-1 function for I2
mode
Source
CT Circuit 1
Protection, Current, Instantaneous
Overcurrent (51-1)
Selects CT circuit 1 as the
source
51-1 Neg
SEQ
Enabled
Target Configuration, Targets
Enables Neg SEQ target
for 51-1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure
65-3.
Blocking is disabled.
OUT1 closes for 51-1 Trip.
OUT2 closes for 51-1 Pickup.
Fault recording is enabled.
Figure 65-3. BESTlogicPlus Settings (I2 Mode)
Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and
send the low range test settings (minimum pickup setting) to the BE1-11m for your sensing input
type in Table 65-10.
Table 65-10. Pickup Test Settings (I2 Mode)
Sensing Input
Type
Range Pickup Setting Time Dial Time Curve
5 A
Low
0.5 A
0
I2
Middle
5.0 A
0
I2
High
9.0 A
0
I2
1 A
Low
0.1 A
0
I2
Middle
1.0 A
0
I2
High
1.8 A
0
I2
Step 4: Prepare to monitor the 51-1 function operation. Operation can be verified by monitoring OUT2
(see Figure 65-3).
Step 5: Connect a current source to terminals D1 and D2 (A-phase). For a single-phase input test, I2 =
Ia / 3. Therefore, the BE1-11m should pick up at a value of three times the setting value when

Table of Contents

Related product manuals