EasyManua.ls Logo

Basler BE1-11m - Page 389

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 65-9
BE1-11m Inverse Overcurrent (51) Test
Table 65-14. Pickup Test Settings (IG Mode)
Sensing Input
Type
Range Pickup Setting Time Dial Time Curve
5 A
Low
0.5 A
0
I2
Middle
5.0 A
0
I2
High
16.0 A
0
I2
1 A
Low
0.1 A
0
I2
Middle
1.0 A
0
I2
High
3.2 A
0
I2
SEF
Low
0.01 A
0
I2
Middle
0.5 A
0
I2
High
0.8 A
0
I2
Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source for protection systems
equipped with two sets of CTs. In step 5, replace D1 with F1, D2 with F2, etc.
Timing Verification (IG Mode)
Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and
send the test settings in Table 65-15 to the BE1-11m .
Table 65-15. Timing Test Settings (IG Mode)
Pickup Setting
Time Curve
0.5 A (5 A sensing), 0.1 A (1 A sensing)
I2
Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time
between a sensing current change and OUT1 closing.
Step 3: Connect a current source to BE1-11m terminals D7 and D8 (IG).
Step 4: Using the values listed in Table 65-16, apply the appropriate current values, and measure the
time between the application of current and the closure of OUT1. Record the results.
Step 5: Repeat step 4 for all of the current and time dial settings for your current sensing type.
Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 51-2, 51-3, 51-4, and 51-5.
Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source for protection systems
equipped with two sets of CTs. In step 3, replace D1 with F1, D2 with F2, etc.

Table of Contents

Related product manuals