EasyManua.ls Logo

Basler BE1-11m - Page 414

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
69-2 9424200996
Power Factor (55) Test BE1-11m
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure
69-1.
Blocking is disabled.
OUT1 closes for 55 Trip.
OUT2 closes for 55 Pickup.
Fault recording is enabled.
Figure 69-1. BESTlogicPlus Settings
Step 3: Use BESTCOMSPlus to open the Protection, Power, Power Factor (55) screen and verify the
first row of test settings in Table 69-2 to the BE1-11m.
Table 69-2. Pickup Test Settings
Lagging Pickup
Leading Pickup
Time Delay
0.5
0.5
60,000 ms
0.99
0.05
0 ms
0.05
0.99
50 ms
Step 4: Prepare to monitor the 55 function operation. Operation can be verified by monitoring OUT1
(see Figure 69-1).
Step 5: Connect and apply 5 A0° to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity)
and a three-phase 69.28 V phase-neutral voltage source to terminals C13 (A-phase), C14 (B-
phase), C15 (C-phase), and C16 (Neutral).
Step 6: Rotate the IA angle in the leading direction until a pickup occurs. This should happen at IA =
VA + cos
-1
(0.5) = +60° ±0.66° (0.49 0.51 PF leading). Decrease the IA angle until OUT1
opens and record the reset. Reset the target.
Step 7: Rotate the IA angle in the lagging direction until a pickup occurs. This should happen at IA =
VA cos
-1
(0.5) = 60° ±0.66° (0.49 0.51 PF lagging). Increase the IA angle until OUT1
opens and record the reset. Reset the target.
Step 8: Verify the pickup accuracy and reset for settings as listed in Table 69-2. Record the results.
Pickup accuracy is ±0.01 PF or equivalently ±|cos
-1
(pickup) cos
-1
(pickup ±0.001)|° of the
associated angle.
Step 9: (Optional.) Repeat steps 1 through 8 for the B-phase and C-phase current inputs taking into
consideration the different current angles. Note: Be sure to enable proper target for each phase
being tested.
Step 10: (Optional.) Repeat steps 1 through 9 for settings group 1, 2, and 3.
Timing Verification
Step 1: Use BESTCOMSPlus to open the Protection, Power, Power Factor (55) screen and send the
first row of test settings in Table 2 for settings group 0.
Step 2: Prepare to monitor the 55 timings. Timing accuracy is verified by measuring the elapsed time
between a sensing voltage change and OUT1 closing.

Table of Contents

Related product manuals