84-30 9424200996
Settings Calculation Examples BE1-11m
and for determining the motor thermal capacity. In this example, set FLA to 3.41 Secondary A and
Service Factor to 1.15. See the manufacturer’s data table at the beginning of this example section. The
BE1-11m Nominal Settings must be set for these secondary units even though the rest of the settings are
in primary.
Figure 84-36. System Parameters, Motor Configuration Screen
System Parameters - Remote Module Communications
RTDs are connected through remote modules connected at the motor. As many as two can be
connected; this example uses one module only. Communication between the BE1-11m and the remote
module must be configured. Use the Settings Explorer to open the System Parameters, Remote Module
Communications screen shown in Figure 84-37. Enable the Status, select Ethernet for Communication
Type, and set Remote Module ID to 1.
The remote RTD module also requires setup. For more information on setting the remote module, refer to
the RTD Module chapter.
Figure 84-37. System Parameters, Remote Module Communications Screen
Programmable Inputs - Remote RTD
RTD Type Selection
This settings example uses nine RTDs that are all 100- platinum construction. Open the Programmable
Inputs, Remote RTD, RTD Type Selection screen shown in Figure 84-38. Select 100 Ohm Platinum for
RTD#1 through RTD#9. Select Disabled for RTD#10 through RTD#12.