BE1-11m Settings Calculation Examples
Figure 84-38. Programmable Inputs, Remote RTD, RTD Type Selection Screen
RTD Block Configuration
For this example, the RTDs are configured into three configuration blocks. Six of the RTDs are used for
stator thermal measurements, two are used for bearing measurements, and one is used for ambient
temperature.
Navigate to Programmable Inputs, Remote RTD, RTD Block Configuration and set RTD Configuration
Blocks 1-3 as shown in Figure 84-39.
Figure 84-39. Programmable Inputs, Remote RTD, RTD Block Configuration Screen