Error handling and diagnostics
EL6752 83Version: 2.1
EL6752-0010 (DeviceNet slave terminal)
LED Color Meaning
RUN green This LED indicates the terminal's operating state:
off State of the EtherCAT State Machine:
INIT = initialization of the terminal;
BOOTSTRAP=function for terminal firmware updates
flashing State of the EtherCAT State Machine:
PREOP = function for mailbox communication and different standard-settings set
Single flash State of the EtherCAT State Machine:
SAFEOP = verification of the sync manager channels and the distributed clocks.
Outputs remain in safe state
on State of the EtherCAT State Machine:
OP = normal operating state; mailbox and process data communication is possible
MNS green green off Slave is offline
flashing Slave port has ended the Duplicate MAC-ID check (Network OK), communication error with
the master.
on Slave port is online and is communicating with the master.
MNS red red flashing Communication error of the slave port with the master, timeout of the slave port
on DeviceNet Bus OFF, DeviceNet voltage error, slave port error, error in Duplicate MAC-ID
check

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff EtherCAT EL6752 and is the answer not in the manual?

Beckhoff EtherCAT EL6752 Specifications

General IconGeneral
BrandBeckhoff
ModelEtherCAT EL6752
CategoryTouch terminals
LanguageEnglish

Related product manuals