Operation and setting
50
TGH1361en/11.2009
5.9 Menu SERVICE
This menu item is provided for the BENDER service personnel and is pro-
tected by a password against erroneous settings. It is intended to provide fast
fault clearance by qualified experts in the event of a device error.
5.10 Parameterization via Internet
The parameters of an IRDH275B indicated below can be checked and set
from a remote place of use by using a personal computer. In addition, a
browser (viewing program for Internet application) and our protocol con-
verter FTC470XET (BMS <==> Ethernet/TCP/IP) are required.
Remote setting is possible for:
z Response value Alarm 1 (1...10,000 kΩ) (Y1)
z Response value Alarm 2 (1...10,000 kΩ) (Y2)
z Operating principle alarm relay 1 (e.g. N/O operation)
z Operating principle alarm relay 2 (e.g. N/O operation)
z Measuring principle (AMP or DC)
z Current output ranges for external measuring instruments (0/4...20 mA)
z Maximum system leakage capacitance (150 μF or 500 μF)
z Time for repetition of the automatic self test (off/ 1 h/ 24 h
z Starting time of the automatic self test (0.00...23.00 h)
z Language of the alarm messages to be displayed (D, GB)
z Setting the fault memory to ON or OFF