EasyManuals Logo

Bender A-Isometer IRDH 275 User Manual

Bender A-Isometer IRDH 275
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
TGH1361en/11.2009
4. Connection
4.1 Wiring
Connect the terminals A1/+ and A2/- to the supply voltage U
S
in accordance
with IEC 60364-4-43. The connections to the supply voltage shall be provid-
ed with protective devices to afford protection in the event of a short circuit
(a 6 A fuse is recommended).
Devices for protection against short-circuit in conformity with IEC 60364-4-
43 for the IT system coupling L1/L2 can be omitted if the wiring is carried
out in such a manner as to reduce the risk of a short-circuit to a minimum (a
short-circuit-proof and earth-fault-proof wiring is recommended).
Only one A-ISOMETER® may be connected to an external TEST or RESET
button. A galvanic parallel connection of several TEST and RESET inputs for
collective testing of A-ISOMETER®s is not permitted.
External coupling devices connected via the terminal AK cannot be switched
off via the internal coupling relays. If no coupling device is used, the terminal
AK remains free.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender A-Isometer IRDH 275 and is the answer not in the manual?

Bender A-Isometer IRDH 275 Specifications

General IconGeneral
BrandBender
ModelA-Isometer IRDH 275
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals