58
P
os
iti
on
of
numbers
from the
left
0 = 1 = 2 = 3 = 4 =
1
N/O operation K1 N/C operation K1 flashing function
2
N/O operation K2 N/C operation K2 flashing function
3
no external coupling AK AGH204S 80K AK AGH520S AK AGH204S 160K AK AGH150W 160K
4
Cemax 1µF Cemax 10µF Cemax 150µF Cemax 500µF
5
Self test without output
relay
Self test with output
relay
6
Self test every 24 hours Self test every hour no periodic self test
7
Language German Language English
8
Password protection not
activated
Password protection
activated
9
AMP measuring
principle
DC measuring
principle
10
max. filter frequency
0.1Hz
max. filter frequency
1Hz
max. filter frequency
10Hz
max. filter frequency
50Hz
11
min. filter frequency
0.1Hz
min. filter frequency
1Hz
min. filter frequency
10Hz
min. filter frequency
50Hz
12
BMS mode Isodata test data
13
Bus address ten's place
(IRDH375B)
14
Bus address unit's
place (IRDH375B)
15
number of pulses 2-9
V a l u e o f t h e r e s p e c t i v e n u m b e r
The parameters presented in italics are settable via the Service menu item ! A password is required for this!