Technical data IRDH375(B)
89
IRDH375_D00124_05_M_XXEN/01.2020
Status number
Value of the respective number
P
os
iti
on
of
numbers
from the
left
0 = 1 = 2 = 3 = 4 =
1
K1: N/O operation Test K1: N/C operation Test K1: flashing function K1: N/O operation K1: N/C operation
2
K2: N/O operation Test K2: N/C operation Test K2: flashing function K2: N/O operation K2: N/C operation
3
no external coupling AK AGH204S 80K AK AGH520S AK AGH204S 160K AK AGH150W 160K
4
Cemax 1 µF ** Cemax 10 µF ** Cemax 150 µF Cemax 500 µF
5
6
Self test every 24 hours Self test every hour no periodic self test
7
Language German Language English
8
Password protection not
activated
Password protection
activated
9
AMP measuring
principle
DC measuring principle
10
max. filter frequency
0.1Hz **
max. filter frequency 1Hz
**
max. filter frequency
10Hz **
max. filter frequency
50Hz **
11
min. filter frequency
0,1Hz **
min. filter frequency 1Hz
**
min. filter frequency
10Hz **
min. filter frequency
50Hz **
12
BMS mode ** Isodata ** test data **
13
Bus address in the tens
place IRDH375
Value: 5 ... 9
14
Bus address in the units
place IRDH375
Value: 5 ... 9
15
Number of pulses 2-9 **
Value: 5 ... 9
** The parameters marked with two asterisks are settable via the Service menu item! A password is required for that
purpose !

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH375 and is the answer not in the manual?

Bender ISOMETER IRDH375 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH375
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals