Operation and setting
67
IRDH375_D00124_05_M_XXEN/01.2020
6.10 Parameterization via Internet
The parameters of an IRDH375B indicated below can be checked and set from
a remote place of use by using a personal computer. In addition, a browser
(viewing program for Internet application) and the BMS Ethernet Gateway
COM465 are required.
Remote setting is possible for:
Response value alarm 1 (1 kΩ…10 MΩ)
Response value alarm 2 (1 kΩ…10 MΩ)
Operating principle alarm relay K1 (e.g. N/O operation)
Operating principle alarm relay K2 (e.g. N/O operation)
Measuring principle (AMP or DC)
Current output ranges for external measuring instruments
(0/4…20 mA)
Maximum system leakage capacitance (150 μF or 500 μF)
Time for repetition of the automatic self test (off/1 h/24 h)
Starting time of the automatic self test (0.00…23.00 h)
Language of the alarm messages to be displayed (D, GB)
Setting the fault memory to "on" or "off"