EasyManua.ls Logo

Bender ISOMETER IRDH375 - Self Test

Bender ISOMETER IRDH375
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function
23
IRDH375_D00124_05_M_XXEN/01.2020
The alarm relays Alarm1/2 only switch after starting the self test function by
pressing the TEST button, that means if an automatic self test has been select-
ed, the alarm relays do not switch.
3.4.2 Relay K3: device fault alarm and EDS common message
Relay K3 is intended to signal device and connection errors of the ISOMETER®.
K3 is permanently set to N/C operation, with the contacts 31-34 normally
closed, that means when a fault occurs, the relay deenergizes (K3: 31-32 con-
nected).
Further details are described in "Chapter 3.4.1 Self test".
Behaviour of the analogue output
The settings for K3 are preset and cannot be adjusted.
Setting Manual test Automatic test
0-20 mA 20 mA
while test procedure
0 mA
The current value depends
on the insulation value
4-20 mA 20 mA
while test procedure
4 mA
The current value depends
on the insulation value

Table of Contents

Related product manuals