EasyManuals Logo

Bender ISOMETER IRDH375 User Manual

Bender ISOMETER IRDH375
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
Operation and setting
60
IRDH375_D00124_05_M_XXEN/01.2020
6.6 Menu COM SETUP: Setting the BMS interface
6.6.1 Bus address „Addr:“ (IRDH375B)
This menu item is used to set the BMS bus address of the IRDH375B. Since
there are several ISOMETER®s in one system, take care that the bus address is
not assigned twice.
The device is factory set to address 3 and hence acts as a Slave.
6.6.2 ISOnet function (IRDH375B)
In the ISOnet = ON sub menu of the COM SETUP, the ISOnet function can be
set. The ISOnet function of all ISOMETER®s existing in the system must be in
"ON" position.
A BMS Master with the ISOnet function activated, controls the ISOnet Slave
devices via the BMS bus. If an ISOMETER® has completed the measuring cycle,
the permission for insulation measurement is given from the ISOnet Master to
the next Slave. During the measurement process carried out by an ISOME-
TER®, all other ISOMETER®s are in the STANDBY mode.
If several IRDH375 are operated on one BMS bus, the
addresses of other ISOMETER®s must be assigned one after
the other, since only one device may represent the Master.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH375 and is the answer not in the manual?

Bender ISOMETER IRDH375 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH375
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals