14.3 Response time profile generator
14.4 Response time profile high capacitance
C
e
≤ 5 µF
C
e
≤ 1 µF
Response time as a function of the response value (R
an
) and system leakage
capacitance (C
e
) according to IEC 61557-8 (U
n
= AC 690 V, f
n
= 50 Hz)
0,1
1
10
100001000100101
Response time [sec]
Response value R
an
[kΩ]
C
e
≤ 1000 µF
C
e
≤ 500 µF
C
e
≤ 150 µF
C
e
≤ 50 µF
C
e
≤ 20 µF
C
e
≤ 5 µF
C
e
≤ 1 µF
Response time as a function of the response value (R
an
) and system leakage
capacitance (C
e
) according to IEC 61557-8 (U
n
= AC 690 V, f
n
= 50 Hz)
10
100
1000
100001000100101
Response time [sec]
Response value R
an
[kΩ]