Factory settings
16. Factory settings
Parameter Value
Response values/alarms
Response value R
an1
(ALARM 1)
40 kΩ
Response value R
an2
(ALARM 2)
10 kΩ
DC alarm off
DC-offset voltage for DC alarm 65 V
Fault memory off
Coupling monitoring on
System
System type 3AC
Profile Power circuits
Time response
Start-up delay T
start-up
0 s
Digital inputs
Digital input 1
Mode (Operating mode) Active high
Function TEST
Digital input 2
Mode (Operating mode) Active low
Function RESET
Digital input 3
Mode (Operating mode) Active high
Function Deactivate device
Digital outputs
Digital output 1
Function 1 off
Function 2 off
Function 3 off
Digital output 2
Function 1 off
Function 2 off
Function 3 off
Switching elements
Relay 1
Test on
Operating mode N/C operation
Function 1 Ins. alarm 1
Function 2 Connection fault
Function 3 off
Relay 2
Test on
Operating mode N/C operation
Function 1 Ins. alarm 2
Function 2 Device fault
Function 3 Connection fault
Interfaces
DHCP off
IP address 192.168.0.5
Net mask 255.255.255.0
BCOM address system-1-0
Device address BS bus 3
ISOnet
ISOnet off
Parameter Value

Table of Contents

Other manuals for Bender ISOMETER iso685-D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER iso685-D and is the answer not in the manual?

Bender ISOMETER iso685-D Specifications

General IconGeneral
BrandBender
ModelISOMETER iso685-D
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals