BENNING IT 115 Technical data
- 57 -
7.4 Loop impedance and prospective short-circuit current
7.4.1 Zs function (for systems without RCD)
Loop impedance
Measuring range according to EN 61557-3: 0.25 9.99 k
Measuring range (
) Resolution (
)
0.00 9.99
0.01
(5 % of the measured value + 5 digits)
10.0 99.9
0.1
100 999
1
10 % of the measured value
1.00 k 9.99 k
10
Prospective short-circuit current (calculated value)
0.00 9.99
0.01
Please observe the accuracy of the loop
resistance measurement.
10.0 99.9
0.1
100 999
1
1.00 k 9.99 k
10
10.0 k 23.0 k
100
The accuracy specified shall apply provided that the mains voltage is stable during measurement.
Testing current (at 230 V) ...................... 6.5 A (10 ms)
Nominal voltage range ........................... 93 V 134 V (45 Hz 65 Hz)
185 V 266 V (45 Hz 65 Hz)
7.4.2 Zsrcd function (for systems with RCD)
Loop impedance
Measuring range according to EN 61557-3: 0.46 9.99 k
Measuring range (
) Resolution (
)
0.00 9.99
0.01
(5 % of the measured value + 10
digits)
10.0 99.9
0.1
100 999
1
10 % of the measured value
1.00 k 9.99 k
10
Accuracy might be impaired due to interference voltages in the mains voltage.
Prospective short-circuit current (calculated value)
0.00 9.99
0.01
Please observe the accuracy of the
loop impedance measurement.
10.0 99.9
0.1
100 999
1
1.00 k 9.99 k
10
10.0 k 23.0 k
100
Nominal voltage range ........................... 93 V 134 V (45 Hz 65 Hz)
185 V 266 V (45 Hz 65 Hz)
No tripping of the residual current protection device (RCD).