101Troubleshooting
Section 12: Troubleshooting
12.8 The Actuator Does Not Stop in Fully Open or
Fully Closed Position
• Check that the actual open and close positions of the valve respectively
correspond to 100% and 0% on the actuator display.
• Make sure that the torque and travel limits are correctly set (see Section 9.1,
Set-up routines - Actuator set-up).
12.9 The Numeric Position Display Indicates “E01”
It is necessary to recalibrate the stroke limits (see Section 9.1, Set-up routines -
Actuator set-up).
12.10 Diagnostic Messages
The alarm and warning lists contain the alarms and warnings momentarily present.
Warning is the condition that occurs when a variable reaches a critical value and/or when a
maintenance action is required but all actuator functions are still available. The ashing of
the alarm/warning LED indicates a warning condition.
Alarm is the condition that occurs when a variable is outside the acceptable range and
some actuator function is not available. If the alarm/warning LED is on there is an alarm
condition. When the fault condition disappears, the corresponding alarm or warning also
disappears from the list.
A reset routine is provided to clear the types of alarms and warnings that are memorized
(over-torque, jammed valve, etc.).
View procedure
• Move the 3-position selector to either OFF or REMOTE, then press NO to scroll the
list of available variables.
• Press YES when the display shows message “ALARMS view?” Press YES to scroll the
list of alarms.
• Press NO when the display shows message “ALARMS view?”
• Press YES when the display shows message “WARNINGS view?” Press YES to scroll
the list of warnings.
• Press YES to reset the alarms or warnings with memory.