September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
43Local Controls
Section 6: Local Controls
6.2 Conguration Options
The F01-2000 actuator can be totally congured from the local interface by means of a
series of menus that can be selected from the alphanumeric display. The operator is guided
through the different displays by answering YES or NO to the appropriate prompt (change?
OK?, view?, next?, etc.) in the right corner of the lower row of the alphanumeric display.
To access the menus: set the local selector in OFF and then simultaneously press OPEN/YES
and STOP. The alphanumeric display will now show the present language. Press YES if the
language is correct, press NO to scroll the list of available languages and then YES to select.
After choosing the language, the next step is the selection among view and set-up mode.
Use “View” mode to see the actuator conguration, and use “Set-up” mode to change
the present conguration. Unauthorized access to the set-up mode is prevented by a
4-character alphanumeric password. The actuator is supplied by Bif with the default
password “0 0 0 0”.
Once the correct password has been entered, the actuator parameters can be congured.
The present password can also be modied by the “set password” routine in the
Maintenance menu. After entering the new password, the old one ceases to be valid, so it is
important to record the password in a secure location for future retrieval.
The conguration functions (view and set-up mode) are grouped in 4 main menus:
Actuator set-up, Nameplate, Valve data, Maintenance.
Actuator set-up
This menu includes the routines that allow the actuator to be congured according to the
requested control mode and to the valve it is mounted on.
stroke limits
torque set-up
ESD set-up
remote controls
local controls
output relays
positioner *
fail-safe *
out 4 - 20 mA *
interlock
2-speed timer
Bus *
miscellaneous
The routines with * are only available if the relevant modules are present. If bus interface is
LonWorks, the “BUS” routine changes to “FDI control”.

Table of Contents

Other manuals for BIFFI F01-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BIFFI F01-2000 and is the answer not in the manual?

BIFFI F01-2000 Specifications

General IconGeneral
BrandBIFFI
ModelF01-2000
CategoryController
LanguageEnglish

Related product manuals