September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
68
Set-Up Routines
Section 9: Set-Up Routines
9.1.12 BUS (or FDI Control)
This routine is only available if a eldbus interface card is present. The routine allows setting
the most important parameters (node address, termination, etc.) necessary to connect
the actuator to a eldbus. If the F01-2000 was set to work with eldbus, but the eldbus
card is not present, a Hardware alarm will be generated. Different interfaces are available
to connect the F01-2000 to different types of eldbus. If the bus interface is LonWorks, the
routine “BUS” changes in “FDI control”. See the specic manuals for instruction and setting
of the above modules.
9.1.13 Miscellaneous
It includes different types of routines as “time and date”, “factory settings”, “lithium
battery”, “torque prole”, etc. used only for special application or in particular conditions.
9.1.13.1 Time and Date
Time and date are used in maintenance functions to associate the time information to the
memorized event (torque prole, alarm log, maintenance request, etc.). Time and date
are entered at the time of manufacture, but they can be adjusted during commissioning or
maintenance operations.
Conguration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions (see
“Entering the set-up mode”). When the message displayed is “SET-UP MODE OK?”
press YES. Press YES to select actuator set-up menu, press NO to scroll the list of
available routines and then press YES to select Miscellaneous.
Press YES to enter the time and date routine.
Press YES if the time is correct, press NO to change it.
Enter hours, minutes and seconds. Press NO to scroll the list of available values,
press YES to select.
Press YES when the time is correct.
Press YES if the date is correct, press NO to change.
Enter day, month, and year. Press NO to scroll the list of available values, press YES
to select.
Press YES if the date is correct.

Table of Contents

Other manuals for BIFFI F01-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BIFFI F01-2000 and is the answer not in the manual?

BIFFI F01-2000 Specifications

General IconGeneral
BrandBIFFI
ModelF01-2000
CategoryController
LanguageEnglish

Related product manuals