September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
69Set-Up Routines
Section 9: Set-Up Routines
9.1.13.2 Factory Settings
The above routine resets the present conguration and restores the default conguration
as below:
Stroke limits Close direction: CW
Close limit: by position
Open limit: by position
Torque set-up Closing torque: 40%
Opening torque: 40%
ESD set-up ESD action: close
ESD signal: present ESD priority:
- ESD < motor thermostat
- ESD < torque limit
- ESD < local stop
- ESD > local controls
- ESD > 2-speed timer
- ESD < OFF
Remote controls Control type: 4 wires latched
Locals controls Control type: latched with instant reverse
LED’s color:
- green = open / opening
- red = close / closing
- yellow = alarm / warning
Output relay Default #1
2-speed timer Opening direction: off
Closing direction: off
Miscellaneous Lithium battery: absent
Torque prole: standard
Torque bypass: 4%
Valve jammed: 4 sec
Table 11.
Conguration procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the actuator set-up menu, press NO to scroll
the list of available routines and then press YES to select Miscellaneous.
• Press No to scroll the list of routines and press YES to select factory conguration.
Press YES to download the standard conguration, press NO to exit.