September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
61Set-Up Routines
Section 9: Set-Up Routines
Auxiliary relays AS1, 2, 3, 4, 5, 6, 7 and 8
Press NO to answer prompt “MONITOR RELAY change?”.
Press YES to change AS1, press NO to select the other relays.
Press YES if the condition associated to AS1 relay is correct, press NO to scrolls the
list of conditions and press YES to set.
Press YES or NO to either conrm or change the type of contact when the
condition occurs (break, make). Since relay AS8 is change-over, this option is
not available.
Press NO to pass to AS2 and then repeat the procedure for the other relays.
Press NO to exit.
9.1.7 Positioner
The positioning function is only available in inching or modulating F01-2000 actuators and
allows to position the valve according to a “position request R%” command signal.
The positioning function compares the present actuator position % with the position
request R%, and if the difference is greater than the dead band the actuator is driven to
reach the new requested position.
The “position request R%” signal may either be received from the bus or the 4 - 20 mA
analog input. If the F01-2000 is set to receive the position request R% from the bus, a
eldbus interface card must be present, or a Hardware alarm will be generated. If the
F01-2000 is set to receive the position request R% from the 4 - 20 mA generator, the
Ain/Aout card must be present, or a Hardware alarm will be generated.
The following options can be congured via local operator interface:
Dead band: congurable from “position resolution%” to 25.5% of the
maximum position error. The congured value should be great enough to avoid
the hunting effect.
Polarity of the 4 - 20 mA position request signal: it allows to reverse the
relationship between the 4 - 20 mA input signal and the “position request R%”,
according to the following diagrams. The option is not available when the
F01-2000 is set to receive the “position request R%” from the bus.
Motion inhibit time: it allows to adjust the length of the delay time between two
cycles of the motor. It can be congured from 1 to 255 s and allows to set the
maximum number of start/hour of the electrical motor.
% MIN and % MAX, 4 - 20 mA input signal range: it allows to change the
relationship between the input signal and the position request R%. This function
is useful when a single 4 - 20 mA signal is used to control the position of 2 valves
(e.g.: split range applications). The option is not available when the F01-2000 is set
to receive the “position request R%” from the bus.

Table of Contents

Other manuals for BIFFI F01-2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BIFFI F01-2000 and is the answer not in the manual?

BIFFI F01-2000 Specifications

General IconGeneral
BrandBIFFI
ModelF01-2000
CategoryController
LanguageEnglish

Related product manuals