September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
60
Set-Up Routines
Section 9: Set-Up Routines
Default #2
Monitor relay
main voltage failure
lost phase
local/off selected
local stop pressed
manual operation
internal temperature alarm
K1 contactor failure
K2 contactor failure
position sensor failure
speed sensor failure
conguration error
HW error
motor over-temperature
over-torque
jammed valve
low lithium battery (if present)
mid-travel alarm
Auxiliary relays
AS1: open limit; break
AS2: close limit; break
AS3: position >90%; break
AS4: position <5%; break
AS5: motor running; make
AS6: remote selected; make
AS7: warning; make
AS8: local selected
Congure output relays
Press YES to change the monitor relay or NO to change auxiliary relays AS1, 2, 3, 4, 5, 6,
7, and 8.
Monitor relay
Press YES or NO to enable or disable the following situations from the conditions which
de-energize the monitor relay: motor over-temperature, over-torque, jammed valve,
manual override, ESD signal on, low lithium battery (if present), local STOP pressed,
LOCAL/OFF selected.