Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
59Set-Up Routines
Section 9: Set-Up Routines
The contacts may be congured to make or break on condition. The options “EFS in
manual”, “EFS mid-travel” and “PST failed” also appear in the menu but are not available
for F01-2000 v4.
Conguration procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select actuator set-up menu, press NO to scroll the
list of available routines and then press YES to select Output relays.
• Press YES to select DEFAULT #1 or press NO to change.
• Press YES to select DEFAULT #2 or press NO to congure the output relays.
Default #1
Monitor relay
• main voltage failure
• lost phase
• local/off selected
• local stop pressed
• manual operation
• internal temperature alarm
• K1 contactor failure
• K2 contactor failure
• position sensor failure
• speed sensor failure
• conguration error
• HW error
• motor over-temperature
• over-torque
• jammed valve
• low lithium battery (if present)
• mid-travel alarm
Auxiliary relays
AS1: open limit; make
AS2: close limit; make
AS3: position >90%; make
AS4: position <5%; make
AS5: motor running; make
AS6: over-torque; make
AS7: ESD active; make
AS8: motor overtemperature