September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
59Set-Up Routines
Section 9: Set-Up Routines
The contacts may be congured to make or break on condition. The options “EFS in
manual”, “EFS mid-travel” and “PST failed” also appear in the menu but are not available
for F01-2000 v4.
Conguration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select actuator set-up menu, press NO to scroll the
list of available routines and then press YES to select Output relays.
Press YES to select DEFAULT #1 or press NO to change.
Press YES to select DEFAULT #2 or press NO to congure the output relays.
Default #1
Monitor relay
main voltage failure
lost phase
local/off selected
local stop pressed
manual operation
internal temperature alarm
K1 contactor failure
K2 contactor failure
position sensor failure
speed sensor failure
conguration error
HW error
motor over-temperature
over-torque
jammed valve
low lithium battery (if present)
mid-travel alarm
Auxiliary relays
AS1: open limit; make
AS2: close limit; make
AS3: position >90%; make
AS4: position <5%; make
AS5: motor running; make
AS6: over-torque; make
AS7: ESD active; make
AS8: motor overtemperature