65Set-Up Routines
Section 9: Set-Up Routines
9.1.9 Out 4 - 20 mA
This routine is only available if the Ain/Aout card is present. With this card the F01-2000 is
provided with a 4 - 20 mA analog input and a 4 - 20 mA analog output.
The 4 - 20 mA output can be congured to provide a current proportional to either
“position” or “torque”. The polarity option allows to reverse the relationship between the
present position or torque and the 4 - 20 mA output signal, according to Figure 48.
Figure 48
OUTPUT: POSITION
POLARITY: 4 mA = CL
Output mA
20 mA
4 mA
Position %
0% 100%
20 mA
4 mA
OUTPUT: POSITION
POLARITY: 4 mA = OP
Output mA
Position %
0% 100%
OUTPUT: TORQUE
POLARITY: 4 mA = CL
OUTPUT: TORQUE
POLARITY: 4 mA = OP
Output mA
Output mA
20 mA
12 mA 12 mA
4 mA
20 mA
4 mA
Torque % Torque %
100% CL 0% 100% OP
100% CL 0% 100% OP
Conguration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “entering the set-up mode”). When the message of the display is “SET-UP
MODE OK?” press YES. Press YES to select the actuator set-up menu, press NO to
scroll the list of available routines and then press YES to select Out 4 - 20 mA.
Press YES if the output is correct (POSITION or TORQUE), or press NO to change it,
then press YES.
Press YES if the polarity is correct, or press NO to change it, then press YES.