EasyManua.ls Logo

BIFFI ICON-030 - Valve Data; Sample Configuration Procedure; Maintenance

Default Icon
177 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
December 2019
70
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Section 9: Set-Up Routines
Set-Up Routines
9.2 Valve Data
The valve data allow identication of the valve and its function in the process. The valve
manufacturer and the end user can enter the data. The following data can be entered:
Tag name (max. 28 characters)
Serial number (max. 28 characters)
Manufacturer (max. 28 characters)
Break OP torque (max. 28 characters)
Break CL torque (max. 28 characters)
Max stem thrust (max. 28 characters)
Flange type (max. 28 characters)
9.2.1 Sample Conguration Procedure
Tag name
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll through the list of available menus and then
press YES to select the "Valve Data" menu.
Press NO to scroll the list of available routines and then press YES to select
"Tag Name".
Press YES if the 1st character of the string is correct. Press NO to scroll through
the list of available characters. Press YES to select the desired character.
Enter up to 28 characters. Enter a blank character, followed by “ ” to mark the end
of the string.
The conguration of all other valve data items is performed in the same way, by selecting
the relevant item from the list of available routines.
9.3 Maintenance
A large amount of data is stored in the actuator memory and is available for future
analysis or to assist the operator in a maintenance program. The maintenance menu also
includes the set password routine and the potential to modify or start the maintenance
functions. The following data are available:
set password
clear alarm log
set torque reference
set curve reference
clear recent data log
set maintenance date
set data logger

Table of Contents